− | Please click here to download the component source project: [https://www.flowcode.co.uk/wiki/componentsource/ | + | Please click here to download the component source project: [https://www.flowcode.co.uk/wiki/componentsource/FC_Comp_Source_temp/ModbusTCP.fcfx FC_Comp_Source_temp/ModbusTCP.fcfx] |
− | Please click here to view the component source code (Beta): [https://www.flowcode.co.uk/FlowchartView/?wfile=componentsource/ | + | Please click here to view the component source code (Beta): [https://www.flowcode.co.uk/FlowchartView/?wfile=componentsource/FC_Comp_Source_temp/ModbusTCP.fcfx FC_Comp_Source_temp/ModbusTCP.fcfx] |
==Detailed description== | ==Detailed description== | ||
Line 126: | Line 126: | ||
In Flowcode each section starts from 0 so the address range is as shown. | In Flowcode each section starts from 0 so the address range is as shown. | ||
+ | |||
+ | |||
Line 134: | Line 136: | ||
==Macro reference== | ==Macro reference== | ||
− | === | + | ===GetResponseByte=== |
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''GetResponseByte''' |
+ | |- | ||
+ | | colspan="2" | Reads a byte from the last received response. The Index parametes specifies which byte to read back. | ||
+ | |- | ||
|- | |- | ||
− | | | + | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE |
+ | | width="90%" | Index | ||
|- | |- | ||
+ | | colspan="2" | 0=SlaveAddress, 1=FunctionCode/ExceptionCode, 2=DataBytes, 3=data0, 4=data1, .. | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE |
− | | width="90%" | | + | | width="90%" style="border-top: 2px solid #000;" | ''Return'' |
+ | |} | ||
+ | |||
+ | |||
+ | ===GetResponseInt=== | ||
+ | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
− | | | + | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] |
+ | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''GetResponseInt''' | ||
|- | |- | ||
− | | | + | | colspan="2" | Reads a 16-bit value from the last received response. The Index parametes specifies the byte index of the value to read back. |
− | |||
|- | |- | ||
− | |||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE |
− | | width="90%" | | + | | width="90%" | Index |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | 3=data0, 5=data1, 7=data2, .. |
|- | |- | ||
− | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9- | + | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u16-icon.png]] - UINT |
| width="90%" style="border-top: 2px solid #000;" | ''Return'' | | width="90%" style="border-top: 2px solid #000;" | ''Return'' | ||
|} | |} | ||
− | === | + | ===ReadAnalogInput=== |
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadAnalogInput''' |
|- | |- | ||
− | | colspan="2" | This command | + | | colspan="2" | This command requests the analogue input register values starting from the start RegAddress and going through to RegAddress plus RegCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
| width="90%" | SlaveID | | width="90%" | SlaveID | ||
|- | |- | ||
Line 178: | Line 189: | ||
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | RegAddress |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Input Address: 0=10001, 1=10002, 2=10003, ... |
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
− | | width="90%" | | + | | width="90%" | RegCount |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Number of consecutive inputs to read, starting from RegAddress |
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 192: | Line 203: | ||
− | === | + | ===ReadCoils=== |
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadCoils''' |
|- | |- | ||
− | | colspan="2" | This command | + | | colspan="2" | This command requests the ON/OFF status of discrete coils starting from the start CoilAddress and going through to CoilAddress plus CoilCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
| width="90%" | SlaveID | | width="90%" | SlaveID | ||
|- | |- | ||
− | | colspan="2" | The ID of the MODBUS slave | + | | colspan="2" | The ID of the MODBUS slave |
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
Line 215: | Line 226: | ||
|- | |- | ||
| colspan="2" | Number of consecutive coils to try and read | | colspan="2" | Number of consecutive coils to try and read | ||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 226: | Line 232: | ||
− | === | + | ===ReadDigitalInputs=== |
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadDigitalInputs''' |
+ | |- | ||
+ | | colspan="2" | This command requests the ON/OFF status of discrete inputs starting from the start DataAddress and going through to DataAddress plus DataCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. | ||
+ | |- | ||
+ | |- | ||
+ | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
+ | | width="90%" | SlaveID | ||
+ | |- | ||
+ | | colspan="2" | The ID of the MODBUS slave | ||
|- | |- | ||
− | | | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
+ | | width="90%" | DataAddress | ||
|- | |- | ||
+ | | colspan="2" | Input Address: 0=10001, 1=10002, 2=10003, ... | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
− | | width="90%" | | + | | width="90%" | DataCount |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Number of consecutive inputs to read, starting from RegAddress |
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 245: | Line 261: | ||
− | === | + | ===ReadHoldingRegister=== |
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadHoldingRegister''' |
|- | |- | ||
− | | colspan="2" | This command requests the | + | | colspan="2" | This command requests the analogue holding register values starting from the start RegAddress and going through to RegAddress plus RegCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
Line 260: | Line 276: | ||
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | RegAddress |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Address: 0=40001, 1=40002, ... |
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | RegCount |
|- | |- | ||
− | | colspan="2" | Number of consecutive | + | | colspan="2" | Number of consecutive registers to read, starting from RegAddress |
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 274: | Line 290: | ||
− | === | + | ===SetCoil=== |
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetCoil''' |
+ | |- | ||
+ | | colspan="2" | This command writes the contents of a discrete coil at the location CoilAddress. Returns 0 for success, 1 for CRC fail and 255 for no reply. | ||
+ | |- | ||
+ | |- | ||
+ | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE | ||
+ | | width="90%" | SlaveID | ||
+ | |- | ||
+ | | colspan="2" | The ID of the MODBUS slave | ||
|- | |- | ||
− | | | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
+ | | width="90%" | CoilAddress | ||
|- | |- | ||
+ | | colspan="2" | Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ... | ||
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE | ||
− | | width="90%" | | + | | width="90%" | CoilState |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | 0=Off, 1=On |
|- | |- | ||
− | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9- | + | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE |
| width="90%" style="border-top: 2px solid #000;" | ''Return'' | | width="90%" style="border-top: 2px solid #000;" | ''Return'' | ||
|} | |} | ||
− | === | + | ===SetCoils=== |
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetCoils''' |
|- | |- | ||
− | | colspan="2" | This command writes the contents of | + | | colspan="2" | This command writes the contents of a series of discrete coils at the location starting at CoilAddress through to CoilAddress + CoilCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE |
| width="90%" | SlaveID | | width="90%" | SlaveID | ||
|- | |- | ||
− | | colspan="2" | The ID of the MODBUS slave | + | | colspan="2" | The ID of the MODBUS slave - Used for TCP to Serial forwarders |
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | CoilAddress |
|- | |- | ||
− | | colspan="2" | Address: 0= | + | | colspan="2" | Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ... |
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | CoilCount |
|- | |- | ||
− | | colspan="2" | Number of consecutive | + | | colspan="2" | Number of consecutive coils to try and read |
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE |
− | | width="90%" | | + | | width="90%" | CoilData |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | An array of bytes each containing 8 1-bit coil values |
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 356: | Line 382: | ||
− | === | + | ===SetHoldingRegisters=== |
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetHoldingRegisters''' |
|- | |- | ||
− | | colspan="2" | This command | + | | colspan="2" | This command writes the contents of several analogue output holding registers starting at the location RegAddress through to location RegAddress + RegCount . Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
Line 373: | Line 399: | ||
| width="90%" | RegAddress | | width="90%" | RegAddress | ||
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Address: 0=40001, 1=40002, ... |
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
| width="90%" | RegCount | | width="90%" | RegCount | ||
|- | |- | ||
− | | colspan="2" | Number of consecutive | + | | colspan="2" | Number of consecutive registers to write, starting from RegAddress |
+ | |- | ||
+ | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
+ | | width="90%" | RegValue | ||
+ | |- | ||
+ | | colspan="2" | Array of values to send to the registers | ||
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 400: | Line 431: | ||
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-void-icon.png]] - VOID | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-void-icon.png]] - VOID | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
| width="90%" style="border-top: 2px solid #000;" | ''Return'' | | width="90%" style="border-top: 2px solid #000;" | ''Return'' | ||
|} | |} |
Revision as of 12:02, 3 February 2023
Author | Matrix Ltd. |
Version | 2.1 |
Category | Comms: System |
Contents
Modbus TCP Master component
Modbus component for talking to Modbus compatible hardware via Ethernet or WIFI. Ensure TCP/IP or WIFI component is initialised and connected to a network before calling the ModbusMasterTCP component macros.
Component Source Code
Please click here to download the component source project: FC_Comp_Source_temp/ModbusTCP.fcfx
Please click here to view the component source code (Beta): FC_Comp_Source_temp/ModbusTCP.fcfx
Detailed description
No detailed description exists yet for this component
Examples
Example master program to control the slave. The example sets coil address 0, clears coil address 0, reads an input register and outputs to the LCD. Be sure to set the IP address of the slave device at the top of the program. If you are simulating then use the IP address of the PC running the Slave simulation. Both programs can be simulated on the same PC using two instances of Flowcode.
Example slave program to react to the signals from the master. The example listens for Modbus commands from the master and outputs the current coils 0 state to an LED connected to PortA. The input register is loaded with a value which is incremented on each Modbus transaction.
Addressing
In Modbus the addressing protocol looks like this.
Data Type | Common name | Starting address | Ending Address | Flowcode Start Address | Flowcode End Address |
Modbus Coils | Bits, binary values, flags | 00001 | 10000 | 0 | 9999 |
Digital Inputs | Binary inputs | 10001 | 30000 | 0 | 19999 |
Analog Inputs | Binary inputs | 30001 | 40000 | 0 | 9999 |
Modbus Registers | Analog values, variables | 40001 | 60000 | 0 | 19999 |
In Flowcode each section starts from 0 so the address range is as shown.
Macro reference
GetResponseByte
GetResponseInt
![]() |
GetResponseInt |
Reads a 16-bit value from the last received response. The Index parametes specifies the byte index of the value to read back. | |
![]() |
Index |
3=data0, 5=data1, 7=data2, .. | |
![]() |
Return |
ReadAnalogInput
ReadCoils
ReadDigitalInputs
ReadHoldingRegister
SetCoil
SetCoils
SetHoldingRegister
SetHoldingRegisters
SetTCPAddress
![]() |
SetTCPAddress |
Sets the address of the remote TCP Slave that we wish to control. | |
![]() |
Address |
e.g. "192.168.1.1" | |
![]() |
Return |